Underfloor heating

Split underfloor heating pipe under a home office floor, Marlborough

The circuit would not hold any pressure. Air at 2 bar could be heard escaping through a wall, and acoustic equipment followed it to one corner of the room.

Hand holding a length of white plastic heating pipe with a long split along its side
The split PEX pipe from the corner of the room, Marlborough job.
Location
Marlborough, Wiltshire (SN9)
Property
Residential property
System
Oil-fired boiler serving underfloor heating downstairs and radiators upstairs; 22mm plastic (PEX) pipe
First sign
Underfloor heating circuit held no pressure at 2 bar
Engineer
James Bexter, ADI Leak Detection
Outcome
Leak found; temporary repair; part re-run in copper

What was happening

The house has an oil-fired boiler running underfloor heating on the ground floor and radiators upstairs. The underfloor heating had been isolated before the engineer arrived because the system was losing pressure.

The plastic pipes are buried in the floor, so looking for the leak was not an option.

How the leak was traced

  1. Air pressure test

    The underfloor heating pipework was disconnected and a compressor put air in at 2 bar. It held nothing, and the air could be heard escaping through the wall on the far side from the test point.

  2. Acoustic listening

    Listening along the floor surface followed the sound of escaping air to one corner of the office room.

  3. Visual inspection

    Once that corner was opened, the leak and the condition of the pipe could be seen directly.

What was found

The leak was a split in 22mm Speedfit PEX pipe buried in the corner of the office room.

What happened next

A temporary repair was made at the leak. The pipe manufacturer does not recommend permanent push-fit fittings on buried plastic pipe of this kind, so the customer was told the repair could not be warranted.

At the customer’s request, the section from the repair back through the wall to the garage was replaced in protected copper. The boiler flow temperature was turned down, and the engineer noted that automatic air vents should be fitted at the high points near the boiler.

The longer-term recommendation is to re-pipe the flow and return to the manifold in copper.

What the repair left to decide

Finding the leak kept the digging to one corner. What to do next depended on the pipe itself, and the customer was given the honest version: a temporary fix now and a recommendation for later.

Underfloor heating leaks: the full guide.

Similar jobs

All case studies

  • Nottingham, Nottinghamshire. Underfloor heating, Screed floor

    Leak in underfloor heating pipes under new screed

    Acoustics and tracer gas were both misled by the way the pipes were laid. Warm water and a thermal camera showed the real pipe route and a faint mark at the leak.

    Leak located; repaired by the site plumbers

  • Battle, East Sussex. Underfloor heating, Screed floor

    The underfloor heating was not the leak

    With underfloor heating everywhere, the heating looked like the obvious suspect. Testing each supply in turn showed the leak was on a hot water T-piece behind a boiler room wall.

    Leak found on the hot supply; fitting replaced; retest held

  • Burnham-on-Crouch, Essex. Underfloor heating, Screed floor

    Salts in the manifold cupboard, paving collapsing outside

    It looked like an underfloor heating leak. Isolation testing put it on the water softener bypass instead, and thermal, acoustic, tracer gas and moisture readings all pointed to one threshold.

    Leak found at the kitchen threshold; copper pipe replaced; retest clear

Call 0333 567 2639

Mon to Fri, 7:30am to 6:30pm