Leak of up to 150 litres an hour under a kitchen screed, Burnham-on-Crouch

It looked like an underfloor heating leak. Isolation testing put it on the water softener bypass instead, and thermal, acoustic, tracer gas and moisture readings all pointed to one threshold.

Small hole cut through floor tiles and dark wet screed, exposing a pipe
Screed opened at the kitchen threshold, Burnham-on-Crouch job.
Location
Burnham-on-Crouch, Essex (CM3)
Property
Large detached house
System
Unvented heating and hot water, underfloor heating in screed
First sign
Meter test showed 80 to 150 litres an hour escaping
Engineer
Mark Jones, ADI Leak Detection
Outcome
Leak found at the kitchen threshold; copper pipe replaced; retest clear

What was happening

Skirting boards and door surrounds were water-damaged and tile grout was discoloured. White salts were pushing up through the screed in the underfloor heating manifold cupboard.

Outside, a section of block paving just inside the gate had collapsed and the grass verge beyond it was waterlogged. A meter test showed between 80 and 150 litres an hour escaping.

How the leak was traced

  1. Flow metering

    Measured the loss at 80 to 150 litres an hour and confirmed the leak was active.

  2. Isolation and pressure testing

    Circuits were isolated one at a time. The leaking one was the water softener bypass supply to the kitchen, not the main underfloor heating circuits.

  3. Thermal imaging

    Showed a temperature anomaly at the threshold between the kitchen and the back hall.

  4. Acoustic listening

    The sound of escaping water matched the spot the thermal camera showed.

  5. Tracer gas

    Gas put into the isolated pipe came up through the screed at the same threshold.

  6. Damp meter

    Mapped moisture across the floor and skirting to separate the leak site from where the water had spread.

What was found

Tiles and screed were lifted at the threshold only. A damaged section of 15mm copper pipe on the softener bypass supply was the cause.

What happened next

The damaged section was replaced and the system retested with no further leak.

The buried pipes were discoloured, which suggests the leak had been going for some time. The engineer advised drying the floor as soon as possible and watching water use during the drying.

Salts at the manifold pointed the wrong way

Salts at the manifold made the heating look guilty. Isolating each circuit first moved the search to a different pipe, and four methods agreeing meant only one threshold was dug up.

Underfloor heating leaks: the full guide.

Similar jobs

All case studies

  • Nottingham, Nottinghamshire. Underfloor heating, Screed floor

    Leak in underfloor heating pipes under new screed

    Acoustics and tracer gas were both misled by the way the pipes were laid. Warm water and a thermal camera showed the real pipe route and a faint mark at the leak.

    Leak located; repaired by the site plumbers

  • Battle, East Sussex. Underfloor heating, Screed floor

    The underfloor heating was not the leak

    With underfloor heating everywhere, the heating looked like the obvious suspect. Testing each supply in turn showed the leak was on a hot water T-piece behind a boiler room wall.

    Leak found on the hot supply; fitting replaced; retest held

  • Marlborough, Wiltshire. Underfloor heating

    Split plastic heating pipe buried in the floor

    The circuit would not hold any pressure. Air at 2 bar could be heard escaping through a wall, and acoustic equipment followed it to one corner of the room.

    Leak found; temporary repair; part re-run in copper

Call 0333 567 2639

Mon to Fri, 7:30am to 6:30pm