Pinhole leak in a heating pipe under living room floorboards, Motherwell

Another engineer had confirmed the system was leaking but not where. Thermal, moisture, acoustic and tracer gas readings agreed on the living room before a single board was lifted.

FLIR thermal camera screen showing a warm spot on a living room floor
Heat spot on the living room floor, Motherwell job.
Location
Motherwell, Lanarkshire (G71)
Property
Two-storey house
System
Combi boiler central heating, copper pipes under suspended floorboards
First sign
Recurring pressure drop; a previous engineer had confirmed a leak but not found it
Engineer
Hamaad Janjua, ADI Leak Detection
Outcome
Pinhole found; section replaced in copper

What was happening

The heating kept losing pressure. An engineer from another company had already confirmed there was a leak but had not located it.

The first physical sign was laminate flooring near the sink that had buckled, suggesting moisture coming up from under the floorboards.

How the leak was traced

  1. Thermal imaging

    Showed a heat spot in the living room: warm water escaping from the heating pipe below.

  2. Moisture meter

    A positive reading in the same area.

  3. Acoustic listening

    Sound consistent with an active leak under the living room boards.

  4. Tracer gas

    A positive result under the living room floor.

  5. Endoscope camera

    With the boards lifted, the camera confirmed the pinhole in the copper pipe.

What was found

A pinhole in the copper central heating pipe under the living room floorboards.

What happened next

The damaged section was cut out and replaced with new copper pipe.

The engineer noted that the pipes under the boards were not properly clipped or insulated and advised putting that right.

Four methods before one board came up

A pressure drop proves there is a leak somewhere. It took four separate methods agreeing to know which boards to lift.

Leaks under floorboards: the full guide.

Similar jobs

All case studies

  • Beccles, Suffolk. Underfloor heating, Floorboards

    Two manifolds, fourteen zones, no visible leak

    With fourteen underfloor zones, the heating was the natural suspect. Testing each section showed the underfloor circuits were sound and the leak was on the radiator pipework.

    Leak found on radiator pipework; fitting replaced; retest passed

Call 0333 567 2639

Mon to Fri, 7:30am to 6:30pm